MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
12
Default: off after an ETS download, and unchanged after a bus power
failure.
Custom: this option brings two new parameters:
•
Initial Status
:
“Previous”, “On”, “Off”, after either an ETS download or a
bus power failure (
last
will be
off
on the very first start-up). When
selecting “On”, the desired
Output Value
needs to be configured, in
terms of percentage.
•
Send Status
: when marked, the status object will be sent to the bus
with a customisable
Delay
, from 0 to 600 ds, 0 to 3600 s, 0 to 1440 min
or 0 to 24 hours (3 seconds by default).
Note
:
the lock status is preserved after a bus failure. In case of conflict
between the state defined for the lock function and the state defined for the
initialization, the lock state prevails. That is, if a bus failure occurs with an
output locked, after the bus recovery the output will have the same value,
independently of the Initial status defined in the Initialization function
.