YSI 5200A
141
YSI 5200A
140
3. When prompted, “Are you sure?”, select one of the following to confirm,
4. Press
to save configuration and return to Run Screen.
Reset Sensors
Menus → System → Service→ Reset To Factory→ Reset Sensors
Specific sensors, aux system, or all sensor and aux systems listed in the Reset Sensors
menu can be reset to factory default.
1. Use
▲
and
▼
to scroll and highlight submenus.
2. Press
to select.
3. When prompted, “Are you sure?”, select one of the following to confirm,
4. Press
to save configuration and return to Run Screen.
Note:
-
Perform a sensor calibration after resetting a sensor to factory default.
Reset Timers
Menus → System → Service→ Reset To Factory→ Reset Timers
A specific timer, feed timer, or all timers listed in the Reset Timers menu can be
reset to factory defaults.
Configuring the 5200A
1. Use
▲
and
▼
to scroll and highlight submenus.
2. Press
to select.
3. When prompted, “Are you sure?”, select one of the following to confirm,
4. Press
to save configuration and return to Run Screen.
Output Test
Menus → System → Service→Output Test
Use the Output Test menu to verify that local relays and remote device relays and
IOEM 4/20mA output channels, are wired and communicating correctly over the
network. Entering this menu turns off any active relays and disables any sensor, aux,
and timer system relays from energizing regardless of value or condition. Systems are
not reset when the Output Test menu is exited. To reset systems after exiting the Relay
Test menu power cycle the 5200A whose output channel was tested. See note below.
Note:
-
Timer and control icon(s) remain at the Run Screen until the system is reset.
Example - the timer icon remains at systemwide location until the end of the
timer cycle that was stopped when the output test menu was entered even
though the relay is not energized. To reset systems after exiting the Relay Test
menu, power cycle the 5200A.
Directions to test outputs
1. Enter Output Test menu
Menus → System → Service→Output Test>Output Test informa-
tion warning window is displayed
2.
at Run Screen to proceed with Output Test. Output Test Menu
opens: