Table 78: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Local Motor
Current Limit
Operator
Standard
Allows the user to specify the maximum allowed motor current (as a
percentage of FLA). When the motor current reaches this value, the Pre-
rotation Vanes will not be permitted to open further. If the motor current
rises above this value, the Pre-rotation Vanes will close to reduce the
current to this value.
Pulldown
Demand Limit Operator
Standard
Allows the user to specify the current limit value (as a percentage of FLA)
to which the chiller will be limited during the specified pulldown limit
time. This value will override the Motor Current Limit value during this
time period. This function is used to provide energy savings following
chiller start-up.
Pulldown
Demand Time Operator
Standard
Allows the user to set a period of time for which the pulldown demand
limit will be in effect after the chiller starts.
kWH Reset
Admin
Admin
Allows the user to reset the cumulative Kilowatt hours to zero (0).
Filter Inhibit
(Harmonic
Filter installed
Only)
Service
JCI Service
Disable the filter logic from activating, although the system will still
communicate with the device. Only available when chiller is stopped.
OptiSave
Service
JCI Service
Moves to a subscreen that displays OptiSave data, OptiSave calculates the
amount of energy a chiller with a VSD will save compared to a Constant
Speed chiller.
Motor Lube
View
View
Moves to the subscreen allowing operator acknowledgement of the
compressor motor lubrication and viewing of the compressor motor
lubrication parameters.
Table 79: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
View
View
Returns the user to Home Screen.
VSD Details
View
View
Navigates to the subscreen that provides more information about the
variable speed drive.
Motor Details
Service
JCI Service
Navigates to a subscreen that provides information and setpoints
pertinent to the Motor Monitoring feature.
Filter Details
(Harmonic
Filter installed
only)
View
View
Navigates to a subscreen that provides more information about the
harmonic filter.
87
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center