Table 95: Display only fields
Field/LED name
Description
Voltage Total Harmonic Distortion
(L1, L2, L3)
Displays the 3-phase voltage Total Harmonic Distortion (THD) measurements.
RMS Filter Current (L1, L2, L3)
Displays the 3-phase filter current values as measured by the Harmonic Filter.
Supply Current Total Demand
Distortion (L1, L2, L3)
Displays the 3-phase Current Total Demand Distortion (TDD) measurements.
RMS Supply Current (L1, L2, L3)
Displays the 3-phase RMS Voltages across each line.
Note:
For fields requiring access level of SERVICE. Service Technicians refer to the
OptiView
Control Center - Service Instructions (Form 160.76-M1)
for operation instructions and explanation
of all programmable setpoints and displayed values.
Table 96: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Local Motor
Current Limit
Operator
Standard
Allows the user to specify the maximum allowed motor current (as a
percentage of FLA). When the motor current reaches this value, the pre-
rotation vanes will not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close to reduce the
current to this value.
Pulldown
Demand Limit Operator
Standard
Allows the user to specify the current limit value (as a percentage of FLA)
to which the chiller will be limited during the specified pulldown limit
time. This value will override the Motor Current Limit value during this
time period. This function is used to provide energy savings following
chiller startup.
Pulldown
Demand Time Operator
Standard
Allows the user to set a period of time for which the pulldown demand
limit will be in effect after the chiller starts.
Table 97: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
View
View
Returns the user to Home screen.
VSD
View
View
Returns the user to VSD screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center