Electromechanical starter screen
Figure 47: Electromechanical starter screen
This screen displays all information pertaining to an Electromechanical Starter.
Table 68: Display only fields
Field/LED name
Description
Motor Run (LED)
Indicates whether the digital output from the controls is commanding the motor to
run.
Motor % Full Load Amps
Displays the motor current as a percentage of the Full Load Amps (FLA) value.
For the Electromechanical Starter, this is the data returned by the CM-2 board.
Current Limit Setpoint
Displays the current limit value in use.
This value could come from a 4 mA to 20 mA, 0 VDC to 10 VDC, PWM signal or SC-EQ
communication interface, or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed pulldown period if the value is
nonzero.
Note:
For fields requiring access level of SERVICE. Service Technicians must refer to the
OptiView Control Center - Service Instructions (Form 160.76-M1)
for operation instructions and
explanation of all programmable setpoints and displayed values.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
80