Parameters
18
RS-485 Communication Setting Menu (Menu: R485) (E1 and E3 terminal area)
Parameter
symbol
Name
Display
level
Setting range
Initial value
PSL
Protocol selection
EASY
PCL: PC link communication
PCLSM: PC link communication
(with checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station
(Loop-1 mode)
CO-S2: Coordinated slave station
(Loop-2 mode)
P-P: Peer-to-peer communication
MBRTU
BPS
Baud rate
EASY
600: 600 bps
1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
19200
PRI
Parity
EASY
NONE: None
EVEN: Even
ODD: Odd
EVEN
STP
Stop bit
EASY
1: 1 bit, 2: 2 bits
1
DLN
Data length
EASY
7: 7 bits, 8: 8 bits
8
ADR
Address
EASY
1 to 99
1
RP.T
Minimum response
time
PRO
0 to 10 (x10ms)
0
When each parameter is displayed, the terminal area (E1 or E3) is displayed on Group display.
• Parameter: PSL, BPS, STP, DLN, ADR, RP.T
18.2 List of Parameters