10-17
IM 05P01D31-01EN
Output
(Control
and
Retransmission)
Functions
(Continued)
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RTH
Maximum
value of
retransmission
output scale of
RET
STD
When RTS = PV1, SP1, TSP1, PV
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When RTS=PV, decimal point position
is same as that of PV input scale.
OUT
RTL
Minimum
value of
retransmission
output scale of
RET
STD
O1RS
Retransmission
output type of
OUT current
output
STD
Same as RTS
O1RH
Maximum
value of
retransmission
output scale of
OUT current
output
STD
When O1RS = PV1, SP1, TSP1, PV
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When O1RS =PV, decimal point
position is same as that of PV input
scale.
O1RL
Minimum
value of
retransmission
output scale of
OUT current
output
STD
Setpoints HOUT1 and COUT1: Can be used in Heating/cooling control.
Setpoint MV1: Can be used in Position proportional control.
(When opening or closing a valve by key operation in manual mode opration, the transmission
output becomes -5.0 %.)
Parameters and Corresponding Terminals
RTS, RTH, RTL
RET/OUT2 terminal
O1RS, O1RH, O1RL
OUT terminal
10
10.11 Setting Retransmission Output Terminal, Type, and Scales
Summary of Contents for UT Advanced UT32A
Page 3: ......
Page 21: ...Blank Page...
Page 35: ...Blank Page...
Page 45: ...Blank Page...
Page 53: ...Blank Page...
Page 89: ...Blank Page...
Page 135: ...Blank Page...
Page 143: ...Blank Page...
Page 255: ...Blank Page...
Page 337: ...Blank Page...
Page 339: ...Blank Page...