17-16
IM 05P01D31-01EN
17.4.10
Heater Break Alarm Wiring
Heater break alarm can be used for the UT35A with the optional suffix code /HA.
Heater break alarm
Heater break detection
Contact raging: 24 V DC, 50 mA
HAL1
HAL2
COM
507
508
509
HBA
Class D grounding
Class D grounding
(grounding resistance
of 100
Ω
or less)
Shield
Shield
CT1
CT2
COM
510
511
512
HBA
Heater break alarm can be used for the UT32A with the optional suffix code /HA.
Heater break alarm
Heater break detection
Contact raging: 24 V DC, 50 mA
HAL1
HAL2
COM
307
308
309
HBA
Class D grounding
Class D grounding
(grounding resistance
of 100
Ω
or less)
Shield
Shield
CT1
CT2
COM
310
311
312
HBA