18-15
IM 05P01D31-01EN
Parameters
18
18.2.2 Setup Parameters
Control Function Setting Menu (Menu: CTL)
Parameter
symbol
Name
Display
level
Setting range
Initial value
CNT
Control type
EASY
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points
of hysteresis)
2P2L: Two-position two-level
control
H/C: Heating/cooling control
Standard type:
PID
Heating/
cooling type:
H/C
ALG
PID control mode
PRO
0: Standard PID control mode
1: Fixed-point control mode
0
SPGR.
Number of SP
groups
STD
1 to 4
4
ALNO.
Number of alarms
PRO
1 to 4
4
ZON
Zone PID selection
STD
0: SP group number selection 1
1: Zone PID selection (selection by
PV)
2: Zone PID selection (selection by
target SP)
3: SP group number selection 2
4: Zone PID selection (selection by
SP)
0
PIDG.
Number of PID
groups
STD
1 to 4
4
18.2 List of Parameters