Errors during Operation (2)
The errors shown below may occur during operation.
PV display
(Operation
Display)
Setpoint display
(Operation
Display)
Status indicator
(Operation
Display)
Parameter
that
displays error
details
Error description
Cause and diagnosis
Remedy
Normal
indication
OUT -----
–
Setup
parameter
(AD2.E)
Feedback input resistor/
current burnout
Feedback input burnout
Check wiring of feedback input resistor/current.
Error indication is erased in normal operation.
Normal
indication
Normal indication LADDER lamp
blinks
Setup
parameter
(LA.ER)
Ladder calculation overflow Floating point computation in ladder calculation
is infinite.
Check the ladder program.
Load factor over 100%
Computation does not end within the control
period (load factor is 100% or more).
Change the control period or reduce the
number of steps for the ladder program.
Load factor over 200%.
(Forced end)
Computation does not end within the control
period (load factor is 200% or more).
Change the control period or reduce the
number of steps for the ladder program.
Ladder program error
Ladder program is corrupted.
Download the ladder program again. If the
error indication is still not erased, there is a
fault. Contact us for repair.
16.1
T
roubleshooting
Summary of Contents for UT Advanced UT32A
Page 3: ......
Page 21: ...Blank Page...
Page 35: ...Blank Page...
Page 45: ...Blank Page...
Page 53: ...Blank Page...
Page 89: ...Blank Page...
Page 135: ...Blank Page...
Page 143: ...Blank Page...
Page 255: ...Blank Page...
Page 337: ...Blank Page...
Page 339: ...Blank Page...