13-3
IM 05P01D31-01EN
Display
, Key
, and Security Functions
13
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PCMD
Active color PV
display switch
EASY
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF:
white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF:
red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm
OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm
OFF: red, Alarm ON: white)
6: PV limit (Within range: white,
Out of range: red)
7: PV limit (Within range: red, Out
of range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation:
red, Out of deviation: white)
10: Link to DI (ON: red, OFF:
white)
DISP
PCH
PV color change
high limit
EASY
Set a display value when in PV
limit or SP deviation.
-19999 to 30000 (Set a value
within the input range.)
Decimal point position depends on
the input type.
PCL
PV color change
low limit
EASY
13.1 Setting Display Functions
Summary of Contents for UT Advanced UT32A
Page 3: ......
Page 21: ...Blank Page...
Page 35: ...Blank Page...
Page 45: ...Blank Page...
Page 53: ...Blank Page...
Page 89: ...Blank Page...
Page 135: ...Blank Page...
Page 143: ...Blank Page...
Page 255: ...Blank Page...
Page 337: ...Blank Page...
Page 339: ...Blank Page...