8-29
IM 05P01D31-01EN
Control Functions
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
ZON
Zone PID
selection
STD
0: SP group number selection 1
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
3: SP group number selection 2
4: Zone PID selection (selection
by SP)
CTL
RP1 to RP3
Reference point 1
to 3
STD
0.0 to 100.0% of PV input range
(EU)
(RP1 ≤ RP2 ≤ RP3)
ZONE
PIDG.
Number of PID
groups
STD
1 to 4
CTL
PID
PID number
(display only)
EASY
1 to 4, R: PID group for reference
deviation
MODE
Note1: A currently-used PID number is displayed for the parameter PID.
Note
When changing the setpoint of the parameter PIDG., if the setpoint of the parameter PIDN
which belongs to the SP menu is larger than that of the parameter PIDG., the PIDN setpoint is
changed to the PIDG. setpoint.
8
8.4 Switching PID