12-1
IM 05P01D31-01EN
Contact Input/Output Functions
12
12.1 Setting Contact Input Function
12.1.1 Setting Contact Input Function
Description
The contact input function works by setting the contact input number (I relay) to functions
such as the operation mode.
This explanation assumes that the contact type is energized. (The function is executed
when the contact is turned on)
AUTO/MAN Switch (A/M)
AUTO/MAN mode can be switched using contact input. (Status switch)
Contact status
Operation
Remark
ON
AUTO
Switch by keystroke or via communication is disabled.
OFF
MAN
Switch by keystroke or via communication is enabled.
REMOTE/LOCAL Switch (R/L)
Displayed only in cases where the communication is specified.
REMOTE/LOCAL mode can be switched using contact input. (Status switch)
Contact status
Operation
Remark
ON
REMOTE
Switch by keystroke or via communication is disabled.
OFF
LOCAL
Switch by keystroke or via communication is enabled.
STOP/RUN Switch (S/R)
STOP/RUN mode can be switched using contact input. (Status switch)
Contact status
Operation
Remark
ON
STOP
When the STOP/RUN switch is assigned (S/R ≠ 0),
switch by keystroke or via communication is disabled.
OFF
RUN
–
Switch to AUTO (AUTO)
The mode can be switched to AUTO using contact input. (Switch by the rising edge)
Contact status
Operation
Remark
OFF→ON
Switch to AUTO
–
ON→OFF
Maintains the current operation status
–
Switch to MAN (MAN)
The mode can be switched to MAN using contact input. (Switch by the rising edge)
Contact status
Operation
Remark
OFF→ON
Switch to MAN
–
ON→OFF
Maintains the current operation status
–
Chapter 12 Contact Input/Output Functions
Summary of Contents for UT Advanced UT32A
Page 3: ......
Page 21: ...Blank Page...
Page 35: ...Blank Page...
Page 45: ...Blank Page...
Page 53: ...Blank Page...
Page 89: ...Blank Page...
Page 135: ...Blank Page...
Page 143: ...Blank Page...
Page 255: ...Blank Page...
Page 337: ...Blank Page...
Page 339: ...Blank Page...