7-6
IM 05P01D31-01EN
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
BS
PV input bias
EASY
-100.0 to 100.0% of PV
input range span (EUS)
PVS
FL
PV input filter
EASY
OFF, 1 to 120 s
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
A.BS
PV analog input bias
STD
-100.0 to 100.0% of each
input range span (EUS)
PV
A.FL
PV analog input filter
STD
OFF, 1 to 120 s
PV
7.1.5 Setting Ratio Bias
Description
Ratio bias computing performs ratio computation and bias addition for remote setpoints.
SP = Remote input x Remote input ratio (RT) + Remote input bias (RBS)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RT
Remote input ratio
STD
0.001 to 9.999
SPS
RBS
Remote input bias
STD
100.0 to 100.0% of PV
input range span (EUS)
Displayed only in cases where the communication is specified.