9-1
IM 05P01D31-01EN
Auxiliary Control Functions
9
9.1 Setting SP Limiter
Description
The SP high and low limits can be set to restrict the SP to the range between those limits
whether in REM (remote) or LCL (local) mode. They works to the SP of all SP groups.
0.0
100.0(%)
Setting range
SPH
Ac
tu
al
S
P
SPL
Setting range of actual SP
Original setting range
0.0
(%)
100.0
High limit of SP
Low limit of SP
► SP group: 6.2 Setting Target Setpoint
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SPH
SP high limit
STD
0.0 to 100.0% of PV input range
(EU), (SPL<SPH)
MPV
SPL
SP low limit
STD
Chapter 9 Auxiliary Control Functions