<4. Operations>
IM 05E01B02-41E
●
Event Display
On the Setpoint display (LCD), the controller displays the event number for which an event
has occurred.
OUT display
Pattern display
Event display
SP display
DISP
key
DISP
key
DISP
key
DISP
key
TME
1
21
3
PVE
ALM
DV-trend /scan=
+
20sec
0
-
PTNO: 1
TM=0h20
SEGNO: 1/ 3
RCY: 0/ 0
SP:
25.0
°
C
Target SP display
DISP
key
PTNO: 1
SEGNO: 1/ 3
SP=
25.0
°
C PID: 1
OUT:
35.0%
PTN
1
SEG
1
Deviation Trend display
DISP
key
PTNO= 1
SEGNO= 1/ 3
SP=
25.0 / 80.0
°
C
For monitoring only.
However, allows the setpoint and segment time
to be changed during hold mode operation
(soak segment).
Allows the control output value to be changed
during manual operation.
For monitoring only.
For monitoring only.
For monitoring only.
For monitoring only.
■
Operating Displays for Single-loop Heating/Cooling Control
●
Setpoint Display
On the Setpoint display (LCD), the controller displays the current target setpoint (SP), the
program pattern number (PTNO) selected, the segment number (SEGNO) for which
operation is in progress, the number of segments included in the selected program pattern,
the remaining time of the segment for which operation is in progress, the current number of
repetitions (RCY), and the total sum of repetitions.
●
Target SP Display
On the Target display (LCD), the controller displays the current target setpoint (SP) and
final target setpoint (TSP), the program pattern number (PTNO) selected, the segment
number (SEGNO) for which operation is progress, the number of segments included in the
selected program pattern, the program pattern name (Only displayed when setting the
program pattern name using an optional parameter setting tool (model: LL100-E10)).