2-8
<Toc>
<2. Initial Settings>
IM 05E01B02-41E
2.3
Changing PV Input Type
The following operating procedure describes an example of changing the setting of K-type
thermocouple (-200.0 to 500.0
⬚
C) to RTD Pt100 (-200.0 to 500.0
⬚
C) and a measurement
range of 0.0 to 200.0
⬚
C.
PV input terminal
Thermocouple/mV/V input..............................
RTD input ..................................................
-
-
13
12
11
-
13
12
1.
Bring the operating display into view (display appears at power-on)
PV
SET/ENT
PT.No
RUN
RESET
DISP
MODE
PVE2
PVE1
PV2
TME
AL
1
1
2
3
4
MAN2
PRG
RST
HLD
LOC
MAN1
CAS
PTNO: 0
TM=-------
SEGNO: 0/ 0
RCY: 0/ 0
SP:
0.0
°
C
RST lamp
ON.
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
1st Edition : May 31,2000-00
2.
Press the
SET/ENT
key for more than 3 seconds
to call up the main menu “PROG”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
programming
main menu
PROG
3.
Press the
key once to display the main
menu “STUP”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
password input
main menu
STUP
4.
Press the
SET/ENT
key once to display the main
menu “PARA”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
setup parameter
SETUP main menu
PARA
5.
Press the
key once to display the main
menu “UPMD”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
SETUP main menu
UP750 configuration
UPMD
6.
Press the
SET/ENT
key once to display the
submenu “MD”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
UP mode set
SETUP sub menu
MD
7.
Press the
key once to display the
submenu “IN”.
SET/ENT
PT.No
RUN
RESET
DISP
MODE
SETUP sub menu
input set
IN