6-20
<Toc>
<6. Parameters>
IM 05E01B02-41E
●
Contact Input Registration Parameters
Located in: Main menu =
CONF
; Submenu =
DI
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Ref.3.1(7)
These parameters determine which contact input to use to
make selections/switches listed on the left.
DI1: 5161
No function: 0
DI2: 5162
DI3: 5163
DI4: 5164
DI5: 5165
DI6: 5166
DI7: 5167
The contact inputs are factory-set as shown below.
Contact inputs 1 to 4 (DI1 to DI4): Program pattern number
selection (see below)
Contact input 5 (DI5): Start of program operation
Contact input 6 (DI6): Stop of program operation
Contact input 7 (DI7): Start of local-mode operation
Program pattern number selection
See “External contact output” in “1.5 Terminal Wiring
Diagrams.”
5165
Stop of program operation
(When “DIn” changes from
OFF to ON)
Start of program operation
(When “DIn” changes from
OFF to ON)
5166
5167
0
5163
5164
0
Start of local-mode operation
(When “DIn” changes from
OFF to ON)
0
Start of hold-mode operation
(When “DIn” changes from
OFF to ON)
Advance of segment
(When “DIn” changes from
OFF to ON)
Bit 2 of program pattern
number
Bit 3 of program pattern
number
PROG
RST
LOC
HOLD
ADV
PTN.2
PTN.3
PTN.4
Bit 4 of program pattern
number
0
MG1
MG2
MG3
MG4
Interruptive message
display 1
0
Interruptive message
display 2
0
Interruptive message
display 3
0
Interruptive message
display 4
0
Loop-2 AUTO/MAN switching
Loop-1 AUTO/MAN switching
(AUTO when contact input is ON;
MAN when contact input is OFF)
0
0
5162
LOCAL/CASCADE switching
Not used for single-loop
control.
5161
Bit 0 of program pattern
number
Bit 1 of program pattern
number
A/M1
A/M2
L/C
PTN.0
PTN.1
DI1
DI2
1
2
3
4
ON
ON
OFF
OFF
ON
ON
OFF
OFF
5
6
7
8
ON
ON
OFF
OFF
ON
ON
OFF
OFF
DI3
DI4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
DI1
DI2
9
10
11
12
ON
ON
OFF
OFF
ON
ON
OFF
OFF
13
14
15
ON
ON
OFF
OFF
ON
ON
DI3
DI4
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
●
UP Mode Parameters
Located in: Main menu =
UPMD
; Submenu =
MD
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Ref.1.1(4)
Ref.1.1(5)
Controller mode
(UP mode)
1: Single-loop control
For another Controller mode, see User’s Manual (Reference)
(CD-ROM version).
1
PV sampling period
setting
100, 200 and 500 ms
The controller restarts if any change is made to the PV sampling
period; this does not affect other parameter settings at all, however.
200 ms
SMP
UPM
Sampling period
error counter
(reading only)
0 to 30000
Shows 0 at
power-on.
SMEC
1st Edition : May 31,2000-00