6-26
<Toc>
<6. Parameters>
IM 05E01B02-41E
●
Communication Parameters
Located in: Main menu =
UPMD
; Submenu =
R485
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Communication
Function
Protocol selection-1
0
PSL1
0: PC link communication
1: PC link communication (with sum check)
2: Ladder communication
3: Coordinated master station
7: MODBUS (ASCII)
8: MODBUS (RTU)
9: Coordinated master station (2 loop mode)
Baud rate-1
600 (0), 1200 (1), 2400 (2), 4800 (3),
9600 (4) (bps)
9600 (4)
Parity-1
NONE (0): None
EVEN (1): Even
ODD (2): Odd
EVEN (1)
Stop bit-1
1, 2
1
Data length-1
7, 8;
7 is fixed for MODBUS (ASCII)
8 is fixed for MODBUS (RTU), Ladder
8
BPS1
PRI1
STP1
DLN1
Minimum response time-1
0 to 10 (
10 ms)
0
RP.T1
Address-1
1 to 99
However, the maximum number of stations
connectable is 31.
1
ADR1
Protocol selection-2
0
PSL2
Minimum response time-2
0 to 10 (
10 ms)
0
RP.T2
Baud rate-2
600 (0), 1200 (1), 2400 (2), 4800 (3), 9600 (4),
19200 (5), 38400 (6) (bps)
9600 (4)
Parity-2
NONE (0): None
EVEN (1): Even
ODD (2): Odd
EVEN (1)
Stop bit-2
1, 2
1
Data length-2
7, 8
8 is fixed for Ladder
8
Address-2
1 to 99
However, the maximum number of stations
connectable is 31.
1
BPS2
PRI2
STP2
DLN2
ADR2
0: PC link communication
1: PC link communication (with sum check)
2: Ladder communication
3: Coordinated master station
5: I/O expansion (for single-controller applications)
6: I/O expansion (for dual-controller applications)
9: Coordinated master station (2 loop mode)
●
Parameter-initializing Parameters
Located in: Main menu =
UPMD
; Submenu =
INIT
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Parameter initialization
OFF (0): -
ON (1): Initialize parameters
OFF (0)
INI