<5. Troubleshooting and Maintenance>
5-3
IM 05E01B02-41E
1st Edition : May 31,2000-00
■
Possible Errors during Operation
The following shows possible errors occurring during operations.
Error indication
Description
of error
PV
Control output
Alarm
output
Retransmis-
sion output
Commu-
nication
Remedy
Displays “RJC” and
PV alternately
RJC error
Measured
with RJC=0
Normal action
ADC error
105%
Faulty
Contact us for repair.
PV burnout error
Dependent on the
BSL parameter
Up-scale: 105%
Down-scale: -5%
In AUTO:
Preset value output
In MAN:
Normal action
Check wires and
sensor.
Excessive PV
Out of -5 to 105%
-5% or 105%
Normal action
Check process.
Auto-tuning
failure
(Time-out)
Action with PID
existing before
auto-tuning
Left end of Setpoint
display unit blinks.
Faulty
communication
line
Check wires and
communication
parameters, and make
resetting. Recovery at
normal receipt
Check process. Press
any key to erase error
indication.
Normal
action
Normal action
Stopped
Normal
action
Normal
action
Normal
action
Normal
action
Decimal point at right end
lights.
Runaway (due to
defective power
or noise)
Undefined
Faulty if power off/on
does not reset start
the unit. Contact us for
repair.
All indications off
Power off
None
0% or less or OFF
OFF
0% or
less
Stopped
Check for abnormal
power.
E200
E300
OVER or -OVER
B.OUT
Feedback resistor
burnout
Check the feedback
resistor.
Stopped
Display position
(Note)
2
1
No display
3
Note 1: PV display
2: Setpoint display
3: Display showing the PV of the corresponding loop
■
Remedies if Power Failure Occurs during Operations
The operation status and remedies after a power failure differ with the length of power
failure time:
●
Instantaneous Power Failure of 20 ms or less
A power failure is not detected. Normal operation continues.
●
Power Failure of about 2 seconds or less
The following show effects caused in “settings” and “operation status.”
Alarm action
Continues. Alarm with standby function will enter standby status.
Settig parameter
Set contents of each parameter are retained.
Auto-tuning Cancelled.
Control action
Action before power failure continues.