<1. Installation>
1-9
IM 05E01B02-41E
Contact Inputs
•
Purpose: Program pattern no. selection, and run/reset switching
•
Number of inputs: 7 points
•
Input type: Non-voltage contact or transistor open collector input
•
Input contact rating: 12 V DC, 10 mA or more
•
On/off determination: For non-voltage contact input, contact resistance of 1 k
or less
is determined as “on” and contact resistance of 20 k
or more as “off.”
For transistor open collector input, input voltage of 2 V or less is determined as “on”
and leakage current must not exceed 100
A when “off.”
•
Minimum status detection hold time: PV input’s sampling period
3
Contact Outputs
•
Purpose: Event output, FAIL output, and others
•
Number of outputs: 7 points
•
Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A
•
Transistor contact rating: 24 V DC, 50 mA
Display Specifications
•
PV display: 5-digit, 7-segment, red LEDs, character height of 20 mm
•
Setpoint display: 32
128 dot LCD with back lighting
•
Status indicating lamps: LEDs
Safety and EMC Standards
•
Safety: Compliant with IEC1010-1: 1990 and EN61010-1: 1992
Approved by CSA1010
CSA1010 installation category (overvoltage category) : CATII (IEC1010-1)
Approved by UL508
•
EMC standards: This instrument complies with the following EMC standards (the
instrument continues to operate at a measuring accuracy of within
20% of the range
during tests):
-
EMI (emission), EN55011: Class A Group 1
-
EMS (immunity), EN50082-2: 1995
1st Edition : May 31,2000-00