C10-3
IM 34M06H62-02E
2nd Edition : June 2008-00
Troubleshooting Errors at Power Up
The following table lists the errors that may be returned by the self-diagnosis procedure
at power up. Check the relevant registers shown in Table C10.1 for the error status.
Table C10.4 Startup Errors
ERR.STUS
(bit pos.)
LED Indicator
Error Condition
Controller
Operation
Measurement Control Output
Troubleshooting Status
RDY ERR
Unknown
Off Off
RAM error
Stops operating.
Unreliable
≤
0% or OFF
Have the module
repaired.
Hardware
failure
Unknown ROM
error
1
Lit
Lit
System data error
2
Calibration value
error
Initializes calibration
value and resumes
normal operation.
Normal
operation
(accuracy is not
guaranteed)
0% or OFF
3
Flashing
Controller or I/O
parameter value
error
Automatically
initializes controller or
I/O parameter and
resumes normal
operation.
Normal
operation
Normal operation
(accuracy is not
guaranteed)
Parameters have been
initialized. Check and
set the parameters
again, as required.
4
Operation parameter
value error
Automatically
initializes operation
parameter and
resumes normal
operation.
Normal operation
Troubleshooting Operation Errors
The tables below list the errors that may be detected during operation. Check the
relevant registers shown in Table C10.1 for the error status.
Table C10.5 Operation Errors (1/2)
ERR.STUS
(bit pos.)
LED Indicator
Error Condition
Controller
Operation
Measurement Control Output
Troubleshooting Status
RDY ERR
5
Lit lit
AD converter error
Normal operation
105%
Automatic: Preset
output
Manual: Normal
operation
*1
Input type setting
Incorrect
wiring
Have the module
repaired.
Hardware
failure
6
RJC error in loop
Operation continues
with reference junction
compensation
disabled.
Reference
junction is
assumed to be
at 0
C.
Normal operation
7 EEPROM
error
Normal operation
continues but
parameter backup to
EEPROM is not done.
Normal
operation
*1
In Cascade Control mode, the control output originates from the secondary loop (even-numbered loop). This error,
however, results in the specified Preset Output. If this error occurs in the primary loop (odd-numbered loop), the
secondary loop is automatically switched to Automatic mode and operation continues.
Table C10.5 Operation Errors (2/2)
ERR.STUS
(bit pos.)
LED Indicator
Error Condition
Controller
Operation
Measurement Control Output
Troubleshooting
Status
RDY ERR
11
Lit
Flashing
PV burnout in loop
Depends on burnout
selection (BSL).
Depends on
BSL burnout
selection.
Automatic: Preset
output
Manual: Normal
operation
*1
Check the sensor and
sensor circuit.
Process
error
12/13 Off
PV
OVER in loop
Continues operation
with PV = 105% or
-5%
Limit values
Normal operation
Check the process.
Unknown Unknown Unknown
Out of control (due
to abnormal power
supply or noise)
CPU resets.
Unknown
≤
0% or OFF
If switching off and on
does not restore normal
operation, have the
module repaired.
Hardware
failure
*1 In Cascade Control mode, the control output originates from the secondary loop (even-numbered loop). This error,
however, results in the specified Preset Output. If this error occurs in the primary loop (odd-numbered loop), the
secondary loop is automatically switched to Automatic mode and operation continues.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...