A2-4
IM 34M06H62-02E
3rd Edition : Jul.16, 2015-00
Table A2.4 Instrument Range and Accuracy (for low resolution operation with SW1-1 set to OFF) 2/4
Input
Categor
y
Input Type
*1
Instrument Range
Input Type Selector Switch
*3
Software
Setting
Accuracy
*4
Resolution
*2
SW1-3 SW1-4 SW5
Software setting
ON
OFF
0
Instrument ranges may be specified by
software using one of the following codes.
Thermoco
uple
K
*5
-200 to1370
C
ON OFF
1 33
($21)
2
C
*5
1
C
*5
-200 to1000
C 2
34
($22)
-200 to500
C 3
35
($23)
2
C 1
C
J
-200 to 1200
C 4
36
($24)
-200 to 500
C 5
37
($25)
T
-270 to 400
C 6
38
($26)
2
C
*6
1
C
B
*7
0
to
1600
C 7
39
($27)
2
C
*7
1
C
*7
S
*8
0 to 1600
C 8
40
($28)
2
C 1
C
R
*9
0
to
1600
C 9
41
($29)
N
-200 to 1300
C A
42
($2A)
2
C
*9
1
C
E
-270 to 1000
C B
43
($2B)
2
C
*10
1
C
*10
L
-200 to 900
C C
44
($2C)
2
C 1
C
U
-200 to 400
C D
45
($2D)
W
*11
0
to
1600
C E
46
($2E)
Platinel 2
0 to 1390
C F
47
($2F)
RT
D
JPt100
-200 to 500
C
ON ON
0 48
($30)
2
C 1
C
-200 to 200
C 1
49
($31)
0 to 300
C 2
50
($32)
0.0 to 150.0
C 3
51
($33)
0.3
C 0.1
C
Pt100
-200 to 850
C 4
52
($34)
2
C 1
C
-200 to 500
C 5
53
($35)
-200 to 200
C 6
54
($36)
0 to 300
C 7
55
($37)
0.0 to 150.0
C 8
56
($38)
0.3
C 0.1
C
*1:
Applicable standard is JIS/IEC/DIN (ITS-90) for thermocouples and RTD.
*2:
For thermocouples K, B, S, R, and W, input ranges may be set wider than their instrument range (see the notes below). Furthermore, the
actual range for an acceptable input is the input range
5%.
*3:
When you turn on the power after changing the hardware switch settings, data stored in the EEPROM is initialized to follow the switch
settings.
*4:
This accuracy applies if the ambient temperature is 25
5
C and the input value is within the instrument range. If the input type is
thermocouple and reference junction compensation is used, you should also take into consideration the accuracy of the reference
junction compensation.
*5:
For K-type thermocouples, the upper and lower input range limits may be set from -270 to 1370
C. The accuracy and resolution depend
on measured temperatures as follows:
-270
to
-200
C: Neither accuracy nor resolution is guaranteed.
*6:
For T-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-270
to
-200
C:
4
C accuracy, 1
C resolution
*7:
For B-type thermocouples, the upper and lower input range limits may be set from 0 to 1800
C. The accuracy and resolution depend on
measured temperatures as follows:
0 to 300
C: Neither accuracy nor resolution is guaranteed.
300 to 900
C:
3
C accuracy, 1
C resolution
*8:
For S-type and R-type thermocouples, the upper and lower input range limits may be set from 0 to 1700
C.
*9:
For N-type thermocouples, the accuracy and resolution depend on measured temperatures as follows:
-200
to
0
C:
3
C accuracy, 1
C resolution
*10: For E-type thermocouples, the detailed accuracy and resolution are as follows:
-270
to
-200
C:
8
C accuracy, 2
C resolution
-200
to
1000
C:
2
C accuracy, 1
C resolution
*11: For W-type thermocouples, the upper and lower input range limits may be set from 0 to 2300
C.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...