C4-2
IM 34M06H62-02E
2nd Edition : June 2008-00
C4.1 Set Point (SP)
Any one of the pre-defined set points (1.SP to 4.SP) or a remote set point (RSP) can be
selected as the control set point (CSP). The set points (1.SP to 4.SP) can be stored in
EEPROM for data retention purposes at power off.
This feature is useful, say, for switching between set point values when switching
production between different product types.
-
Set the Set Point (1.SP to 4.SP) parameters to different set point values.
- For a loop in Single-Loop or Two-input Changeover mode, or the primary loop in
Cascade control mode, set the Remote/Local Selection (RMT/LOC) parameter to 0
(Local).
- For the secondary loop in Cascade Control mode, set the Automatic/Manual/
Cascade Selection (A/M/C) parameter to Automatic.
- To change the set point, select the desired Set Point parameter using the SP
Number Selection (SPNO) parameter.
-
To see which SP number is currently selected, read the CSPNO parameter.
Changing the SPNO parameter in local mode operation selects the following parameters
(where n denotes the value of SPNO and is an integer ranging from 1 to 4).
- n.SP
Set
Point
-
n.A1 Alarm 1 Preset Value
-
n.A2 Alarm 2 Preset Value
-
n.A3 Alarm 3 Preset Value
-
n.A4 Alarm 4 Preset Value
TIP
If the Zone PID Selection (ZONE) parameter is set to ‘0: Disabled’, changing the SP Number Selection
(SPNO) also changes the PID constants, including PB, TI and TD. For details on the parameters that are
changed, see Section C6.9, “PID Selection Method”.
Table C4.1 SP-related Parameters
Data Position Number
Symbol Description
Unit
Data
Range
Default
Value Attribute Stored
Loop1 Loop2 Loop3 Loop4
103
303
503
703
CSP
Control set point
Industrial Unit PRL to PRH
—
RO
—
107
307
507
707
CSPNO Current SP number
None
1 to 4
—
RO
—
122 322 522 722 A/M/C
Automatic/manual/
cascade selection
None
0: Automatic
1: Manual
2: Cascade
*1
0 RW —
124 324 524 724 RMT/LOC
Remote/local
selection
None
0: Local
1: Remote
0 RW —
128 328 528 728 SPNO SP
number
selection
None 1 to 4
1
RW
—
201
401
601
801
1.SP
Set point
Industrial Unit PRL to PRH
PRL
RW
Irregular
221
421
621
821
2.SP
Set point
Industrial Unit PRL to PRH
PRL
RW
Irregular
241
441
641
841
3.SP
Set point
Industrial Unit PRL to PRH
PRL
RW
Irregular
261
461
661
861
4.SP
Set point
Industrial Unit PRL to PRH
PRL
RW
Irregular
*1
The controller mode must be set to Cascade Control before Automatic/Manual/Cascade Selection (A/M/C) can be set
to 2 (Cascade). In cascade control mode, operation proceeds according to the setup for the even-numbered loop
(2 or 4).
- You need to execute a specific procedure every time to update stored set point
values. Otherwise, stored set points will not be updated so the parameters revert to
their last stored values whenever the module is turned off and then on again. For
details, see Section B2.4, "How to Back up SP Values to EEPROM."
- For F3CU04-
N, set points (1.SP to 4.SP) are always automatically stored to
EEPROM when updated. Updating set points frequently may damage the EEPROM
stoarge media. Therefore, if the set point is to be changed continually (as a ramp
signal, for example), you should make use of the remote set point (RSP) instead.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...