![YOKOGAWA F3CU04-0S User Manual Download Page 189](http://html1.mh-extra.com/html/yokogawa/f3cu04-0s/f3cu04-0s_user-manual_3485079189.webp)
C6-3
IM 34M06H62-02E
2nd Edition : June 2008-00
Adjusting the Proportional Band
When fine-tuning a proportional band obtained from auto-tuning, or when adjusting the
proportional band manually, note the following points.
-
Always adjust downwards from a larger value to a smaller value.
-
If oscillations appear, it means that the PB setting is too small.
- Adjusting the proportional band will not eliminate the offset. (Adjusting the Integral
Time (TI) and Manual Reset (MR) parameters may however eliminate the offset.)
Figure C6.4 Adjusting the Proportional Band
Table C6.2 Proportional Band Parameter
Data Position Number
Symbol Description
Unit
Data Range
Default
Value
Attribute Stored
Loop1 Loop2 Loop3 Loop4
206
406
606
806
1.PB
Proportional band
%
1 to 9999 (0.1 to 999.9%)
50
RW
226
426
626
826
2.PB
Proportional band
%
1 to 9999 (0.1 to 999.9%)
50
RW
246
446
646
846
3.PB
Proportional band
%
1 to 9999 (0.1 to 999.9%)
50
RW
266
466
666
866
4.PB
Proportional band
%
1 to 9999 (0.1 to 999.9%)
50
RW
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...