C2.4 Control Types and their Operations
Two control types are available: ON/OFF control output and PID control output.
C2.4.1 ON/OFF Control Output
In ON/OFF control, the module turns on or off an output according to the deviation
between the control set point (CSP) and the PV. To set the control type to ON/OFF
Control, set the Control Type Selection (OT) parameter to 1. For details, see Section
C2.1, “Control Type Selection."
Table C2.6 I/O Registers related to ON/OFF Control
Data Position Number
Symbol Description Unit
Data
Range
Default
Value Attribute
Stored
Loop 1 Loop 2 Loop 3 Loop 4
212 412 612 812
1.HYS
ON/OFF control
hysteresis
Industrial
unit
0 to (PRH - PRL)
(PRH - PRL) x 0.5%
RW
232 432 632 832
2.HYS
RW
252 452 652 852
3.HYS
RW
272 472 672 872
4.HYS
RW
Table C2.7 Input Relays related to ON/OFF Control
Input Relay Number
X
nn
*1
Symbol
Description
Data Range
Loop1
Loop2
Loop3
Loop4
X05
X13
X21
X29
HOUT.R Heating control output
0: OFF
1: ON
*1
denotes the slot number where the module is mounted.
The hysteresis parameters specify the minimum deviation of the PV from the control set
point, or the hysteresis that will trigger an ON-to-OFF or OFF-to-ON output transition.
The hysteresis is set for each controller loop in industrial unit. The following description of
hysteresis assumes that the Forward/Reverse Switch parameter is set to Reverse
Control. For details on forward control and reverse control, see Section C6.1, “Forward
Operation and Reverse Operation"
Figure C2.2 Schematic Diagram of ON/OFF Control (for reverse operation)
In ON/OFF control mode, the output turns off only when the PV exceeds the CSP by a
certain amount, and turns on again when PV is less than the CSP by a certain amount,
as shown by the arrows in the figure. The difference between the PV at which the output
turns off and the PV at which the output turns on is called hysteresis. If the hysteresis is
too small, chattering (output turning on and off too frequently) may occur. Increase the
hysteresis to prevent chattering as necessary.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...