C6-17
IM 34M06H62-02E
2nd Edition : June 2008-00
Reference Deviation
The Reference Deviation (RDV) parameter allows you to switch between PID parameter
groups according to the magnitude of the deviation.
When the difference between the PV and CSP is larger than the value of the Reference
Deviation (RDV) parameter, the PID parameter group intended for large deviations is
selected (PIDNO = 4).
For instance, when the deviation is large, proportional band can be reduced to bring the
PV to the CSP more quickly.
PID parameter group switching by the Reference Deviation (RDV) parameter has priority
over switching by the Reference Point (1RP, 2RP) parameters. In addition, when the
deviation falls below the Reference Deviation (RDV), operation reverts to using the Zone
PID parameter group corresponding to the PV at that point.
The Zone Switching Hysteresis (RHY) parameter applies when a switchover from PID
parameter group 1, 2 or 3 to PID parameter group 4 is made due to reference deviation.
Table C6.11 Parameters Related to Reference Deviation
Data Position Number
Symbol Description
Unit
Data
Range
Default
Value Attribute Stored
Loop1 Loop2 Loop3 Loop4
189
389
589
789
RDV Reference deviation Industrial unit
0 to (PRH-PRL)
Setting to 0 disables the
reference deviation function.
0 RW
Figure C6.16 Reference Deviation Selection
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...