Heating/Cooling Control Output Limits
The upper limit of the heating output is defined with the Upper Output Limit (n.OH)
parameter (where n: 1-4), and the upper limit of the cooling output is defined with the
Lower Output Limit (n.OL) parameter (where n: 1-4). The lower limit of the heating or
cooling output is fixed at 0%.
Table C2.18 Heating/Cooling Control Output Limits
Data Position Number
Symbol Description Unit
Data
Range
Default
Value
Attribute Stored
Loop 1 Loop 2 Loop 3 Loop 4
209
409
609
809
1.OH Upper output limit
%
0 to 1050 (0.0 to 105.0%)
1000 RW
210
410
610
810
1.OL
Lower output limit
1000
RW
229
429
629
829
2.OH Upper output limit
%
0 to 1050 (0.0 to 105.0%)
1000 RW
230
430
630
830
2.OL
Lower output limit
1000
RW
249
449
649
849
3.OH Upper output limit
%
0 to 1050 (0.0 to 105.0%)
1000 RW
250
450
650
850
3.OL
Lower output limit
1000
RW
269
469
669
869
4.OH Upper output limit
%
0 to 1050 (0.0 to 105.0%)
1000 RW
270
470
670
870
4.OL
Lower output limit
1000
RW
In Automatic mode, depending on the dead band and cooling gain preset values,
sometimes the cooling output will never reach the Lower Output Limit (n.OL) (n: 1-4).
TIP
In Automatic mode of heating/cooling PID control, the output range is defined by restricting the PID
computation result within upper and lower limits that are calculated from the specified upper and lower
output limits as follows:
- Upper limit for PID computation result =
upper output limit (n.OH) (n: 1-4)/2 + dead band [%]/2 + 50%
- Lower limit for PID computation result =
50% - lower output limit (n.OL) (n: 1-4)/(2 x cooling gain) - dead band [%]/2
where the dead band is converted from industrial unit to percentage as follows:
Dead band [%] = ((dead band in industrial unit)/(PRH - PRL) x 100%) x 100%/(proportional band x 2).
The PID computation result is further restricted within
200%. Therefore, even if the computed lower
limit for PID computation result is less than -200%, the PID computation result is still limited by -200%
and so is the cooling output.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...