C3-17
IM 34M06H62-02E
2nd Edition : June 2008-00
Automatic Changeover Using Upper Limit (SELMD: 1)
In this mode, Input 1 is used when it is not higher than SELH, and Input 2 is used when
Input 1 is higher than SELH, as follows:
Input 1
SELH: Input 1 is selected.
Input 1 > SELH: Input 2 is selected.
Manual Changeover Using Input Selection (SELMD: 2)
Switches between input 1 and input 2 according to the Input Selection (INSEL)
parameter, as follows:
INSEL = 0: Input 1 is selected.
INSEL = 1: Input 2 is selected.
The PV may change abruptly when changeover is made between Input 1 and Input 2,
as illustrated below.
1
0
Input 2
Input 1
PV
INSEL
0
Figure C3.8 Changeover Using Input Selection (INSEL) Parameter
TIP
If two inputs have different values, switching between the two inputs would result in an abrupt change in
controlled output. To prevent this, this mode uses the average of the two inputs as the PV value within the
overlapping range. For this to work in Automatic Changeover Using Temperature Range mode (SELMD
= 0), you must define input 1 and input 2 with overlapping ranges.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...