9 Operation
9.9.3 Adjusting the Force Reference Offset
9-62
Use the following procedure for automatic adjustment of the force reference offset.
(2) Manual Adjustment of the Force Reference Offset
Manual adjustment of the force reference offset (Fn00B) is used in the following cases.
• If a position loop is formed with the host controller and the error is zeroed when servolock is stopped.
• To deliberately set the offset to some value.
• Use this mode to check the offset data that was set in the automatic adjustment mode of the force reference
offset.
This mode operates in the same way as the automatic adjustment mode (Fn009), except that the amount of offset
is directly input during the adjustment.
The offset adjustment range and setting units are as follows:
Step
Display after
Operation
Digital
Operator
Panel
Operator
Description
1
Turn OFF the SERVOPACK, and input the 0-V reference volt-
age from the host controller or external circuit.
2
Press the DSPL/SET or MODE/SET Key to select the utility
function mode.
3
Press the LEFT/RIGHT or UP/DOWN Key, or UP or DOWN
Key to select parameter Fn009.
*The digit that can be set will blink.
4
Press the DATA/ENTER Key once, or DATA/SHIFT Key for
more than one second. “rEF_o” will be displayed.
5
Press the DSPL/SET or MODE/SET Key.
The reference offset will be automatically adjusted.
When completed, “donE” will blink for about one second.
6
About one second later
After “donE” is displayed, “rEF_o” will be displayed again.
7
Press the DATA/ENTER Key once, or DATA/SHIFT Key for
more than one second to return to the Fn009 display of the util-
ity function mode.
SERVOPACK
Servo OFF
0-V force
reference
Host
controller
Linear servomotor
Slow movement
(Servo ON)
DSPL
SET
(DSPL/SET Key)
MODE/SET
(MODE/SET Key)
DATA
ENTER
(DATA/ENTER
Key)
DATA
(DATA/SHIFT Key)
(Press at least 1 s.)
DSPL
SET
(DSPL/SET Key)
MODE/SET
(MODE/SET Key)
DATA
ENTER
(DATA/ENTER
Key)
DATA
(DATA/SHIFT Key)
(Press at least 1 s.)
Offset Adjustment Range: -
128 to +127
(Force reference: -1881.6 mV to +1866.9 mV)
Force Reference
Offset Adjustment
Range
Offset Setting Unit
Analog
Input
Voltage
Offset Setting Unit
Force reference:
1 = 14.7 mV