7 Wiring
7.5.4 Operating Conditions on 400-V Power Supply Voltage
7-36
7.5.4 Operating Conditions on 400-V Power Supply Voltage
There are three types of SGDH SERVOPACKs, for the power supply voltages: Single-phase 200 VAC, three-
phase 200 VAC, and three-phase 400 VAC. When using the SERVOPACK for 200 V with the three-phase 400-
VAC class (380 to 480 V), prepare the following voltage conversion transformers (single-phase or three-phase)
When selecting a voltage conversion transformer, refer to the capacities shown in the following table.
* This is the net value at the rated load.
Single-phase Power Supply Connection Example
• Do not connect the SERVOPACK for 200 V directly to a voltage of 400 V.
The SERVOPACK will be destroyed.
• Control the AC power supply ON and OFF sequence at the primary side of voltage conversion transfer.
Voltage conversion transfer inductance will cause a surge voltage if the power is turned ON and OFF at the secondary,
damaging the SERVOPACK.
CAUTION
Primary Voltage
Secondary Voltage
380 to 480 VAC
→
200 VAC
Voltage
SERVOPACK Model
SGDH-
Voltage Capacity per
SERVOPACK * (kVA)
Current Capacity of Circuit
Breaker or Fuse (Arms)
Single-phase
200 V
A5AE
0.25
4
01AE
0.40
02AE
0.75
04AE
1.2
8
Three-phase
200 V
05AE
1.4
4
08AE
1.9
7
10AE
2.3
15AE
3.2
10
20AE
4.3
13
30AE
5.9
17
50AE
7.5
28
75AE
15.5
41
Single-phase
Magnetic contactor for
power supply ON and OFF
Voltage conversion
transformer
200 VAC
SERVOPACK
R
S
T
1KM
1KM
L1
L2