B.2 Parameter Tables
156
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
o1-02
(501H)
User Monitor
Selection after
Power Up
Power-On Monitor
1: Frequency Ref
2: FWD/REV
3: Output Freq
4: Output Current
5: User Monitor
Selects the information displayed on the digital operator
when the power is turned on.
1: Output Voltage Feedback
2: Input Voltage
3: Power Supply Current
4: Power Supply Power
5: User monitor item set in o1-01
Default: 1
Min.: 1
Max.: 5
o1-05
(504H)
LCD Contrast
Control
LCD Contrast
Sets the brightness of the LCD operator (option).
Default: 3
Min.: 0
Max.: 5
o2: Digital Operator Keypad Functions
o2-01
(505H)
LO/RE Key
Function Selection
LO/RE Key
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and
REMOTE operation.
Default: 1
Min.: 0
Max.: 1
o2-02
(506H)
STOP Key Function
Selection
Oper STOP Key
0: Disabled
1: Enabled
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Min.: 0
Max.: 1
o2-03
(507H)
User Parameter
Default Value
User Default Sel
0: No Change
1: Save User Init
2: Clear User Init
0: No change.
1: Set defaults. Saves parameter settings as default values
for a User Initialization.
2: Clear all. Clears the default settings that have been
saved for a User Initialization.
Default: 0
Min.: 0
Max.: 2
o2-04
(508H)
Unit Model
Selection
Inverter Model #
Enter the regenerative unit model. Setting required only if
installing a new control board.
Default:
Determined by unit
capacity.
Min.: –
Max.: –
o2-06
(50AH)
Operation Selection
when Digital
Operator is
Disconnected
Oper Discon Det
0: Disabled
1: Enabled
Determines the operation when the digital operator is
disconnected.
0: The regenerative unit continues operating if the digital
operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min.: 0
Max.: 1
o2-09
(50DH)
Reserved
–
–
–
o2-21
(81AH)
Unit Check
US signal check
0: Nomal
1: Start
Sets the operation for Unit Capacity Setting Error (oPE01).
Set this parameter to 1 to reset an oPE01 fault without
cycling the power supply.
0: Standard
1: Recheck regenerative unit (The parameter returns to 0
after it is set.)
Default: 0
Min.: 0
Max.: 1
o3: Copy Function
o3-01
(515H)
Copy Function
Selection
COPY SELECT
0: COPY SELECT
1: INV
→
OP READ
2: OP
→
INV WRITE
3: OP
←→
INV
VERIFY
0: No action
1: Read parameters from the regenerative unit, saving them
onto the digital operator.
2: Copy parameters from the digital operator, writing them
to the regenerative unit.
3: Verify parameter settings on the regenerative unit to
check if they match the data saved on the operator.
Default: 0
Min.: 0
Max.: 3
o3-02
(516H)
Copy Allowed
Selection
Read Allowable
0: Disabled
1: Enabled
0: Read operation prohibited
1: Read operation allowed
Default: 0
Min.: 0
Max.: 1
o4: Maintenance Monitor Settings
o4-01
(50BH)
Cumulative
Operation Time
Setting
DrvElapsTimeCnt
Sets the value for the cumulative operation time of the
regenerative unit in units of 10 h.
Default: 0
Min.: 0
Max.: 9999
o4-02
(50CH)
Cumulative
Operation Time
Selection
ElapsTimeCntSet
0: Power-On Time
1: Running Time
0: Logs power-on time
1: Logs operation time when the regenerative unit output is
active (output operation time).
Default: 0
Min.: 0
Max.: 1
No.
(Address
Hex)
Name
LCD Display
Description
Values
TOEP_C710656_10B_1_0.book 156 ページ 2015年1月8日 木曜日 午後8時55分