B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
155
Pa
ra
me
te
r L
is
t
B
◆
o: Operator-Related Settings
The o parameters set up the digital operator displays.
L8-10
(4B6H)
Heatsink Cooling
Fan Operation
Selection
Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On
0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the
regenerative unit is powered up.
Default: 0
Min.: 0
Max.: 1
L8-11
(4B7H)
Heatsink Cooling
Fan Off Delay Time
Fan Delay Time
Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.
Default: 60 s
Min.: 0 s
Max.: 300 s
L8-12
(4B8H)
Ambient
Temperature Setting
Ambient Temp
Enter the ambient temperature. This value adjusts the oL2
detection level.
Default: 40
°
C
Min.: -10
°
C
Max.: 50
°
C
L8-35
(4ECH)
Installation Method
Selection
Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
2: IP20/NEMA Type 1
3: ExternalHeatsink
0: IP00 Open Type Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1
3: External Heatsink Installation
Min.: 0
Max.: 3
L8-41
(4F2H)
High Current Alarm
Selection
High Cur Alm Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled. An alarm is triggered at output currents above
150% of regenerative unit rated current.
Default: 0
Min.: 0
Max.: 1
L8-65
(66FH)
Power Supply Fault
Detection Selection
Vpn Ripple Sel
0: Disabled
1: Coast to Stop
2: Alarm Only
There is normally no need to change this parameter from
the default value.
Monitors the ripple of DC BUS voltage and detects Input
Power Supply Fault(PF2) when the ripple is too bad.
0: No detection
1: Stop operation (fault)
2: Continue operation (minor fault)
Default: 0
Min.: 0
Max.: 2
L8-66
(670H)
Power Supply Fault
Detection Voltage
Level
Vpn Ripple Lvl
There is normally no need to change this parameter from
the default value. The main circuit DC voltage ripple is
monitored in a cycle of 200 ms. If the difference between
the maximum and minimum values of the ripple exceeds
the value that is set in L8-66 for the number of times that is
set in L8-67, a power supply fault is detected.
200 V Class
Default:
Min.: 1
Max.: 200
400 V Class
Default:
Min.: 1
Max.: 200
L8-67
(671H)
Number of Times of
Power Supply Fault
for Detection
Vpn Ripple Cnt
Default: 5
Min.: 1
Max.: 10
L8-69
(673H)
Input Phase Loss
Protection Selection
3
AC Phase Imb Det
0: Disabled
1: Enabled
Sets whether to enable or disable the protective function
for the regenerative unit when there is an input phase loss.
0: Disabled
1: Enabled (Detect input phase loss and power supply
imbalance.)
Default: 1
Min.: 0
Max.: 1
<2> Default setting is dependent on parameter o2-04, Unit Model Selection.
No.
(Address
Hex)
Name
LCD Display
Description
Values
o1: Digital Operator Display Selection
o1-01
(500H)
Drive Mode Monitor
Selection
User Monitor Sel
When the power supply is turned on, the operator will
display the following in order: DC Bus Voltage Feedback
Reference, Input Voltage, Power Supply Current, Power
Supply Power, Power Supply Frequency, and U1-
.
The o1-01 parameter sets the item to display instead of the
output voltage.
The o1-02 parameter sets the item to display at power up.
Default: 158
(Monitor U1-58)
Min.: 110
Max.: 914
No.
(Address
Hex)
Name
LCD Display
Description
Values