B.2 Parameter Tables
154
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
◆
L: Protection Function
Protection function parameters set momentary power loss processing, fault retries, and hardware protection.
No.
(Address
Hex)
Name
LCD Display
Description
Values
L2: Momentary Power Loss Ride-Thru
L2-01
(485H)
Momentary Power
Loss Operation
Selection
PwrL Selection
0: Disabled
1: Enbl with Timer
2: Enbl whl CPU act
0: Disabled. Regenerative unit trips on Uv1 fault when
power is lost.
1: Recover within the time set in L2-02. Uv1 will be
detected if power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
Note:
Even if L2-01 is set to 1 or 2, the regenerative unit
may detect a fault when momentary-power-loss occurs
during regeneration or during no load.
Default: 0
Min.: 0
Max.: 2
L2-02
(486H)
Momentary Power
Loss Ride-Thru
Time
PwrL Ridethru t
Sets the Power Loss Ride-Thru time. Enabled only when
L2-01 = 1 or 3.
Default:
Min.: 0.0 s
Max.: 25.5 s
L2-05
(489H)
Undervoltage
Detection Level
(Uv)
PUV Det Level
There is normally no need to change this parameter from
the default value.
200 V Class
Default: 190 V
Min.: 150 V
Max.: 210 V
400 V Class
Default: 380 V
Min.: 300 V
Max.: 420 V
L2-21
(4D5H)
AUv Detection
Level
AC UV Level
Sets the undervoltage detection level for power supply
voltage (AC) in volts.
200 V Class
Default: 150 V
Min.: 100 V
Max.: 200 V
400 V Class
Default: 300 V
Min.: 200 V
Max.: 400 V
L2-38
(11E3H)
Power Supply
Frequency
Excessive Deviation
Pre-alarm
pFDV DetectCount
Sets the number of times the regenerative unit detecting
PFDv (Power Supply Frequency Excessive Deviation
Pre-alarm). Disabled when set to 0.
Default: 4
Min.: 0
Max.: 30
L5: Fault Restart
L5-01
(49EH)
Number of Auto
Restart Attempts
Num of Restarts
Sets the number of times the regenerative unit may attempt
to restart after the following faults occur: oC, oH1, oL2,
ov, Uv1.
Default: 0 time
Min.: 0 time
Max.: 10 times
L5-02
(49FH)
Auto Restart Fault
Output Operation
Selection
Restart Sel
0: Flt Outp Disabld
1: Flt Outp Enabled
0: Fault output not active.
1: Fault output active during restart attempt.
Default: 0
Min.: 0
Max.: 1
L5-04
(4A0H)
Fault Reset Interval
Time
Flt Reset Wait T
Sets the amount of time to wait between performing fault
restarts.
Default: 10.0 s
Min.: 0.5 s
Max.: 600.0 s
L5-05
(46CH)
Fault Reset
Operation Selection
Fault Reset Sel
0: Continuous
1: Use L5-04 Time
0: Continuously attempt to restart while incrementing
restart counter only at a successful restart.
1: Attempt to restart with the interval time set in L5-04 and
increment the
restart counter with each attempt.
Default: 0
Min.: 0
Max.: 1
L8: Drive Protection
L8-02
(4AEH)
Overheat Alarm
Level
OH Pre-Alarm Lvl
An overheat alarm occurs when heatsink temperature
exceeds the L8-02 level.
Default:
Min.: 50
°
C
Max.: 150
°
C
L8-03
(4AFH)
Overheat Pre-Alarm
Operation Selection
OH Pre-Alarm Sel
0: Ramp to stop
3: Alarm only
0: Ramp to stop. A fault is triggered.
3: Continue operation. An alarm is triggered.
Default: 3
Min.: 1
Max.: 3
L8-07
(4B3H)
Input Phase Loss
(PF3) Protection
Selection
Phase Loss Det
0: Disabled
1: Enabled
Default: 1
Min.: 0
Max.: 1
TOEP_C710656_10B_1_0.book 154 ページ 2015年1月8日 木曜日 午後8時55分