6.4 Cooling Fans
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
119
Pe
ri
odic
Ins
p
ec
tion &
Ma
inte
na
nce
6
4.
Remove the fan guard and replace the cooling fans.
Note: 1.
Do not pinch the fan cable between parts when reassembling the fan unit.
2.
Install the internal circulation fans so that they blow air upward. Install the cooling fan so that it blows air downward.
Figure 6.15
Figure 6.15 Fan Unit Disassembly
Cooling Fan Wiring: 2A0053, 4A0053, 4A0073
1.
Position the protective tube so the fan connector sits in the center of the protective tube.
2.
Place the fan connector covered by the tube.
Figure 6.16
Figure 6.16 Cooling Fan Wiring: 2A0053, 4A0053, 4A0073
3.
Make sure that the protective tube does not stick out beyond the fan guard.
A – Fan guard
C – Cooling fan (Air flow: Upward)
B – Cable cover
D – Circulation fan (Air flow: Downward)
A
C
D
B
A
C
Airflow
Airflow
Airflow
2A0053, 2A0073, 4A0053 to 4A0150
2A0105, 4A0210, 4A0300
Protective tube
次回用
Connector for fan B1
Fan B1
Fan B2
2A0050
㧘
4A0060
4A0100
Connector for fan B2
次回用