5.5 Operator Programming Errors
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
101
Tr
oub
le
sho
o
ti
n
g
5
Digital Operator
Display
Error Name
Detail
oPE05
Run Command
Selection Error
The settings for the Run Command or Bus Voltage Command are not correct.
Cause
Possible Solutions
The Run Command Selection 1 is assigned to
an option card (b1-02 = 3) and an input option
card is not connected to the unit.
Reconnect the input option card to the regenerative unit.
Digital Operator
Display
Error Name
Detail
oPE07
Multi-Function Analog
Input Selection Error A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06.
Cause
Possible Solutions
At least two of these parameters have the same
setting: H3-02, H3-10, or H3-06.
Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.
Note:
Both 1F (Through mode) and F (Through mode) can be set to H3-02, H3-10, or H3-06
simultaneously.
Digital Operator
Display
Error Name
Detail
oPE30
Incorrect Input Voltage
Adjustment
The input voltage offset adjustment has not been performed.
Cause
Possible Solutions
• The setting of o2-04 (Unit Model Selection)
changed.
• ERPROM failed for the input voltage offset.
For information on clearing the fault, consult with your Yaskawa representative or the nearest
Yaskawa sales office.