B.2 Parameter Tables
150
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
24 to 27
2C to 2F
External fault
External fault
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
3C
Forced Operation Command
Manual Run
Closed: Starts the operation of the regenerative unit.
3D
Automatic Operation
Command
Auto Run
Closed: The regenerative unit starts to operate when the voltage of the bus
increases (i.e., when a regenerative state is reached).
47
Node Setup
Node SetUp
Closed: Node setup for SI-S3 enabled.
67
Communications test mode
Comm Test Mode
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays
“PASS” if the test completes successfully.
No.
(Address
Hex)
Name
LCD Display
Description
Values
H2: Multi-Function Relay Outputs
H2-01
(40BH)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to
H2 Multi-Function Relay Output Settings on
for a description of setting values.
Note:
Set unused terminals to F.
Default: 26
Min.: 0
Max.: 160
H2-02
(40CH)
Terminal P1-PC
Function Selection
(Photocoupler)
P1/PC Func Sel
Default: 6
Min.: 0
Max.: 160
H2-03
(40DH)
Terminal P2-PC
Function Selection
(Photocoupler)
P2/PC Func Sel
Default: 25
Min.: 0
Max.: 160
H2-06
(437H)
kWh Monitor Pulse
Output Unit Selection
Pwr Mon Unit Sel
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Select the output unit of the multi-function contact when
H2-01 to H2-03 is set to 3A.
1: 1 kWh
2: 10 kWh
3: 100 kWh
4: 1000 kWh
Default: 1
Min.: 1
Max.: 4
H2 Multi-Function Relay Output Settings
H2-
Setting
Function
LCD Display
Description
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
6
Operation Ready
Drive Ready
Closed: Power up is complete and the regenerative unit is ready to accept
a Run command.
7
DC bus undervoltage
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
8
During baseblock (N.O.)
BaseBlk 1
Closed: Regenerative unit has entered the baseblock state (no
regeneration).
E
Fault
Fault
Closed: Fault occurred.
F
Through mode
Not Used
Set this value when using the terminal in the pass-through mode.
10
Minor fault
Minor Fault
Closed: An alarm has been triggered.
11
Fault reset command active
Reset Cmd Active
Closed: A command has been entered to clear a fault via the input
terminals or from the serial network.
H1 Multi-Function Digital Input Selections
H1-
Setting
Function
LCD Display
Description
TOEP_C710656_10B_1_0.book 150 ページ 2015年1月8日 木曜日 午後8時55分