Service and Maintenance
77
Replaceable Parts
Below is a list of components of the ECO detector that are field serviceable and/or
replaceable together with the Xtralis part/order number for the each.
Part
Xtralis Part/Order Number
Filter Cartridge Assembly
LF41333
USB access port Rubber Bung
LF41291
USB Connection Lead
LF41313
VESDA ECO Product Guide
LF41308
Sensor Cartridge O-Ring
LF41301
Filter Cartridge O-Ring
LF41303
microSD Card (2GB)
LF41312
Sensor Cartridge
To avoid any confusion, use the part
number indicated on the label fitted to the
exterior of the Sensor Cartridge that is to
be replaced, NOT the one on the main
product label.
Detector Removal
To remove the entire ECO Detector from the installed pipe work, follow these
instructions.
1. Disable the VESDA detector which is the source of the ECO air flow
2. Invoke the Stand-by Mode on the VESDA detector to shut down the
aspirator.
3. Isolate the power connection to the ECO Detector.
4. Depress the Cover latch on the side of the main body, then lift the cover
and slide away from the detector body. This will reveal the ECO power and
communications cabling. Mark up all of the associated cabling to the ECO
terminals, and detach all of the cable connections. Slide the cabling out of
the ECO main body through the bulkhead grommets.
5. If fitted, remove the pipe inserted in the gas test port.
6. With the cables and gas test port pipe detached, remove the detector body
from the sampling pipe work. The ECO detector is now free and can be
serviced and or replaced as necessary.