VESDA ECO Detector by Xtralis
Product Guide
17898_05
Troubleshooting
67
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2006
Sensor module RAM
failure . An internal
Memory error has occurred
in the Cartridge
N
The Sensor cartridge suffered an internal memory failure try to reboot. If unable to
clear replace sensor cartridge and re commission
2007
Sensor module
configuration write failed .
An internal Memory error
has occurred in the
Cartridge
N
The Sensor cartridge suffered an internal software failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2008
Sensor module
configuration read failed .
An internal Memory error
has occurred in the
Cartridge
N
The Sensor cartridge suffered an internal software failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2009
Sensor Cartridge software
fault
N
The Sensor cartridge suffered an internal software failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2010
Sensor module not present
The sensor Module is not
Responding To
Communication requests
N
The detector has not recognised the sensor cartridge. Check sensor cartridge is
inserted the correct way round and is seated correctly. Click clear to reset. If
unable to clear error replace the sensor cartridge and or the main PCB and
reconfigure / commission detector.