Troubleshooting
63
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2032
Configuration change
rejected
Y
The detector has rejected the previous change to the configuration on the basis of
either insufficient access rights or the value written falls outside the permissible
limits for that configuration variable
2033
Calibration Failed
Signal too noisy or
calibration gas is outside
acceptable tolerance limits
Y
Sensor cartridge failed to calibrate.
Check calibration gas, connections and settings then recalibrate. If error persists,
replace sensor cartridge and re-commission
2034
Flow Normalization Failed
The air flow is not stable
enough to allow calibration
Y
Sample air flow was not stable during the commissioning procedure. Check ECO
detector inlet and outlets for obstructions. Check ECO sensor filter assembly for
damage or contamination. Check ASD and sample air pipe work installation and
re-commission. If error persists and ASD is in good operation replace main
sensor cartridge and reconfigure / re-commission
2035
The air temperature is
greater than the
specification permits
Y
The detector has been exposed to temperatures above it's specified operating
temperature. Check sample air temperature. Click clear to reset. If unable to reset
and sample air temperature is within specified limits replace sensor cartridge and
re-commission. If unable to clear error replace complete detector and re
commission.
2036
The air temperature is less
than the specification
permits
Y
The detector has been exposed to temperatures below its specified operating
temperature. Check sample air temperature. Click clear to reset. If unable to reset
and sample air temperature is within specified limits, replace sensor cartridge and
re-commission. If still unable to clear the error, replace complete detector and re
commission.