VESDA ECO Detector by Xtralis
Product Guide
17898_05
Troubleshooting
71
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2142
Zero calibration failed
Signal too noisy or
calibration gas is outside
acceptable tolerance limits
Y
Sensor cartridge failed to calibrate zero level.
Check calibration gas, connections and settings then recalibrate. If error persists,
replace sensor cartridge and re-commission
2143
Span calibration failed
Signal too noisy or
calibration gas is outside
acceptable tolerance limits
Y
Sensor cartridge failed to calibrate span.
Check calibration gas, connections and settings then recalibrate. If error persists,
replace sensor cartridge and re-commission
2144
Calibration due.
Within 2 weeks of next due
calibration date
Y
The sensor cartridge is within 2 weeks of needing recalibration. Recalibrate
sensor cartridge.
2145
Calibration out of date.
Calibration Due Date has
passed
Y
The sensor cartridge is out of calibration. Recalibrate.
2106
Gas under range.
Sensor more than 10% (of
range) below the defined
minimum range (Zero)
Y
An ECO gas sensor is experiencing negative zero drift. Click reset to clear. If
unable to clear re zero / calibrate sensor cartridge. If error persists replace sensor
cartridge.