Heat Exchanger
8.1
Typical Closed Loop Cooling System (if applicable)
8.2
Internal Heat Exchanger (if applicable)
COOLING WATER SUPPLY Max Flowrate: 7.9 gal/min [30 l/min]
COOLING WATER SUPPLY Min Flowrate: 4.0 gal/min [15 l/min]
COOLING WATER SUPPLY Max Pressure: 145 psi [10 bar]
Estimated Pressure Drop: 1.0 psi [0.07 bar] COOLING WATER SUPPLY-TO- RETURN.
Maximum COOLING WATER SUPPLY Temperature: 140° F [60° C]
Maximum COOLING WATER RETURN Temperature: 160° F [71° C]
Oil Sump Capacity: Approximately 9.25 gal [35 l]
COOLING WATER i
nlet/Outlet Connection: 1”
-11 BSPP male
COOLING WATER flow Direction: Bi-Directional
•
COOLING WATER SUPPLY and COOLING WATER RETURN can be switched if needed.
Direction of flow is not important.
Cooling medium: COOLING WATER SUPPLY may be fresh water or fresh water with up to a
50/50 ethylene glycol mixture. Do NOT use propylene glycol.