1. General
See start of document.
2. Safety
See start of document.
3. Transport and interim storage
The pump may only be transported/suspended
on the handle provided for transport. It is
to be protected against humidity, frost and
mechanical damage.
4. Product and accessory description
4.1 Applications
Pumps for lifting of domestic waste water:
– sewage, rainwater containing sludge and parti-
cles (except rigid particles) with traces of hydro-
carbon, detergent.
– For fixed installation in a sump or a tank.
– For housing, garages, car-parks, restaurants,
boiler plants.
Submersible pumps with a mains connection
cable of less than 10 metres are (according to EN
60335) only permitted for use inside buildings,
i.e. not for operating outside.
CAUTION! The pump must not be used for
pumping drinking water.
4.2 Description (see Fig. 1-2)
1 Check valve adapted to the conveyed medium
2 Isolating valve
3 Overflow audible signal
4 Pump lifting chain
5 Motor cable - length 5 m
6 Collector for twinned pump.
4.3 Description of pump
– Submersible monobloc electropump,
– Centrifugal single-stage with vortex impeller,
– Vertical discharge port,
– Tightness with mechanical seal and lip seal.
4.4 Description of motor
– Single-phase motor equipped with a built-in motor
cut-out, which switches the motor off if it over-
loads and automatically switches it back on again
once it has cooled down; delivered with electric
cable-length 5 m with a CEI 23-5 plug and float
switch. Integrated capacitor
– Three-phase motor delivered with float switch and
electric cable, length 5 m without plug.
– Protection index: IP68
– Insulation class: B
– Oil-cooled motor.
4.5 Products delivered
– Submersible motor-driven pump complete,
– Installation and operating instructions.
4.6 Accessories
Accessories must be ordered separately.
– Isolating valve,
– Non-return valve,
– Float switch,
– Lifting chain,
– switchbox for the automatic transmitter-
dependent control of one or two submersible
motor-driven pumps,
– Alarm switching device.
5. Product Information
When ordering spare parts, please give all the
information on the pump rating plate.
6. Assembly/Installation
6.1 Installation
– Fig. 1: Installation of a pump with single-phase
motor, float switch and optional overflow audible
signal.
– Fig. 2: Fixed installation of 2 pumps connected
to a collector for twinned pumps and operating-
contol by 4 float switches.
NOTICE:
Cut-out level:
For intermitted duty:
H min = 40 mm short-term,
For continuous duty:
H1 min = 230 mm (Fig. 1-2)
The shaft should be of ample size, so that the
motor does not start too often.
NOTICE:
Lower the pump into the sump using a chain (or a
rope) hooked to the handle, never by its power-
or float switch cable.
Take care not to damage the power cable of the
motor during the going down in the sump.
Avoid placing the regulators near the outlet of
the pipe through which the water enters the
sump, since this could mover them.
Power consumption P1 [kW]
see rating plate
Motor-output P2 [kW]
see rating plate
Nominal current I [A]
see rating plate
Protection class at max. immersion depth
IP68
Insulation class
B
Immersion depth (
8
) max. [m]
2
Temperature range [°C]
3 to 40
Max. particle size [mm]
Ø 40
Equipment
Cable type
H07RN-F
Cable length [m]
5
Float switch
connected
Pressure support DN
11/2”
Level control (Fig. 1, 2)
Shaft dimension
š
min [mm]
450 x 450
Cut-out level continuous duty H1min [mm]
230
Cut-out level intermittent duty (short-term) Hmin [mm]
40
Installation and operating instructions - Wilo-Drain TC40