Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
6 Operation
83309302 1/2018-05 La
92-196
Activate measurement
Switch on system at switch S1 [ch. 5.7].
Select
combustion chamber pressure
and confirm.
Set combustion chamber pressure to
On
and confirm.
The fan drives to maximum fan speed.
Deactivate measurement
After 10 minutes or after exiting the parameter, the combustion chamber pressure
is automatically reset to
Off
.
Set function of parameter
10.5.1.4 input H1
.
If necessary, set parameter
10.5.1.5 input H1 inverted
.
Switch off system using switch S1 [ch. 5.7].
Install ionisation electrode.
If necessary, plug in plug H1/H2.
Mount the front panel and secure the tension lock with the screw.