Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
12 Technical documentation
83309302 1/2018-05 La
163-196
12.10 Sensor variables
Flow sensor (eSTB) WTC
Flue gas sensor WTC
DHW sensor (B3)
DHE sensor switch-on (B3)
De-couple sensor (B2)
Plate heat exchanger (B2)
DHW outlet sensor (T1)
DHW sensor switch-off (T2)
Flow sensor (B6)
Return circulation (T1)
External sensor WTC (B1)
External sensor heating circuit (T1)
NTC 5 kΩ
NTC 2 kΩ
°C
Ω
°C
Ω
-20
48 180
-20
15 138
-15
36 250
-15
11 709
-10
27 523
-10
9 138
-5
21 078
-5
7 193
0
16 277
0
5 707
5
12 669
5
4 563
10
9 936
10
3 675
15
7 849
15
2 981
20
6 244
20
2 434
25
5 000
25
2 000
30
4 029
30
1 653
35
3 267
35
1 375
40
2 665
40
1 149
45
2 185
50
1 802
55
1 494
60
1 245
65
1 042
70
876
75
740
80
628
85
535
90
457
95
393
100
338
105
292
110
254