Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
7 Commissioning
83309302 1/2018-05 La
105-196
7.2 Adjusting the condensing unit
Depending on system variation, specific commissioning steps are shown or hidden.
For cascade operation or multiple assignment, note deviating settings for commis-
sioning, see installation and operating manual Flue gas-air system.
During commissioning, make sure that:
maximum possible water throughput is ensured,
heat up is carried out with low flow temperatures and at low rating.
Open gas isolating valve.
Switch on system at switch S1 [ch. 5.7].
The commissioning wizard can be restarted at any time during the initial commis-
sioning.
Press dial knob for approx. 15 seconds.
The system device can be reset to its factory setting.
Reset device to factory setting.
The commissioning wizard restarts.
1. Set language
Select language required and confirm.
The language selected is generated.
The commissioning wizard starts.
Language
Deutsch
English
Français
Italiano
Español
Nederlands
OK = Press
Commissioning
The commissioning wizard guides you step
by step through the commissioning.
Select
and confirm.
2. Set date and time
Select
year
,
month
or
day
.
Press dial knob.
Selected area is highlighted in blue.
Set current date and confirm.
Select
and confirm.
Select
hours
or
minutes
.
Press dial knob.
Selected area is highlighted in blue.
Set current time of day.
Date
2016
June
23
Year
Month
Day
Time of day
16
55
Time of day
: