Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
10 Troubleshooting
83309302 1/2018-05 La
137-196
The following faults must only be rectified by qualified personnel:
Fault
Cause
Rectification
F 32
De-couple sensor (B2) defective
Check the sensor and cable and replace if neces-
sary
F 33
External sensor (B1) defective
Check the sensor and cable and replace if neces-
sary
F 34
DHW sensor (B3) defective
Check the sensor and cable and replace if neces-
sary
F 36
System pressure outside of range
Check system pressure, if necessary top up or
drain.
F 38
T1 sensor at additional module de-
fective
Check the sensor and cable and replace if neces-
sary
F 39
T2 sensor at additional module de-
fective
Check the sensor and cable and replace if neces-
sary
F 40
Internal pump signals electronic
fault
Check circulation pump, replace if necessary.
F 41
Gas valve control faulty
Check gas combi valve and cable, replace if ne-
cessary.
F 42
Internal pump signals blockade fault
Check circulation pump, replace if necessary.
F 43
Specified fan speed is not achieved
Check the fan and cable, replace if necessary.
F 44
Fan standby defective
Check the fan and cable, replace if necessary.
F 45
Valve flows out of tolerance
Check gas combi valve and cable, replace if ne-
cessary.
F 46
Multifunction sensor VPT defective
Purge system (heating circuit and DHW circuit).
Purge unit on the water side, initiate program
Automatic purging
Increase system pressure.
Install the deaerator on site.
Check multifunction sensor VPT and cable, re-
place if necessary.
F 47
Multifunction sensor VPT version er-
ror
Version of multifunction sensor VPT not compatible
with appliance electronics WEM-FA-G
Replace multifunction sensor.
F 49
Data record error burner control
Interrupt the voltage supply temporarily
Carry out
BCC Update
Replace appliance electronics WEM-FA-G if oc-
curring repeatedly.
F 50
Internal fault
Interrupt the voltage supply temporarily
Reset appliance, replace appliance electronics
WEM-FA-G if occurring repeatedly.
F 51
Data record error boiler
Interrupt the voltage supply temporarily
Carry out
BCC Update
Replace appliance electronics WEM-FA-G if oc-
curring repeatedly.
F 52
Data record error burner
Interrupt the voltage supply temporarily
Carry out
BCC Update
Replace appliance electronics WEM-FA-G if oc-
curring repeatedly.
F 53
Voltage supply outside the tolerance
limits
Check voltage supply
F 54
Electronic fault
Interrupt the voltage supply temporarily
Reset appliance, replace appliance electronics
WEM-FA-G if occurring repeatedly.