12.5 Inputs/outputs
The inputs and outputs can be configured for various functions [ch. 6.6.9.5].
Depending on the hydraulic variant selected, the inputs and outputs are pre-as-
signed, the function can then not be changed [ch. 12.1].
WTC output MFA1, VA1 and VA2
Setting
Explanation
Off
Output not used.
Forward reporting of
operation
The contact closes as soon as a flame signal is present.
Safety valve Gas
The contact closes as soon as heat demand is present.
Forward reporting of
faults
The contact closes as soon as a fault occurs.
Actuator heating and
DHW mode
(1
The contact is closed during heating and DHW mode.
Actuator DHW mode
(1
The contact is closed during DHW mode.
Actuator heating mode
(1
The contact is closed during heating mode.
DHW 1: actuator
The contact is closed during DHW loading of DHW circuit 1.
Switched output via App
Variable contact via an App. Not supported in the current software version.
Pump neutralisation
The contact closes as soon as a flame signal is present.
(1
Actuator: circulation pump or three-way valve
WTC input H1
The function (contact position) of input H1 can be rotated using parameter
Input
H1 inverted
.
Setting
Explanation
Off
Input not used.
System standby with
frost protection
The WTC is disabled for heating and DHW mode when the contact is closed.
Frost protection is activated.
Emergency-Off
heat exchanger
The system is disabled for heating and DHW mode when the contact is open.
Frost protection is not activated.
This function can be used to connect a temperature monitor, underfloor heating
circuit or safety switch of a condensate lift unit.
Block heating/
DHW mode
The WTC is disabled for heating and DHW mode when the contact is closed.
Frost protection is activated.
Generator block
heating mode
The WTC is disabled for heating mode when the contact is closed. Frost protec-
tion is activated.
Heating circuit 1:
standby
Heating circuit 1 is disabled for heating mode when the contact is closed. Frost
protection is activated.
Heating circuit 1: set-
back
When the contact is closed, the system heats to setback setpoint. The heating
program of heating circuit 1 is ineffective.
Heating circuit 1: nor-
mal
When the contact is closed, the system heats to normal setpoint. The heating pro-
gram of heating circuit 1 is ineffective.
Heating circuit 1: com-
fort
When the contact is closed, the system heats to comfort setpoint. The heating
program of heating circuit 1 is ineffective.
Heating circuit 1:
Emergency-Off
Heating circuit 1 is disabled for heating mode when the contact is open. Frost pro-
tection is not activated.
Heating circuit 1:
special level
When the contact is closed, the system heats to special level. The heating pro-
gram of heating circuit 1 is ineffective.
Forward signalling via
portal
When the contact is closed, a message is forwarded to the WEM portal.