Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
11 Accessories
83309302 1/2018-05 La
145-196
Refitting
Replace seal
4
ensuring sealing surfaces are clean.
Refit externally powered anode in reverse order and:
place the green surface of the diode board
3
in such a way it faces nut
2
,
tighten screws with a torque of 8 Nm.
Fit inspection flange, tighten screws diagonally across (35 Nm +5).
Connect anode cable
1
.
CAUTION
Corrosion due to missing protective layer
Incorrectly connected externally powered anode does not form a protective layer. A
missing protective layer can lead to corrosions.
Correctly connect cable
1
.
1
4
3
2
Plug in mains adapter.
Control lamp on mains adapter illuminates green.
Check anode current (greater than 1 mA), enter value and date on label.
Enter completed service on label.
Refit front panel.