Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
6 Operation
83309302 1/2018-05 La
98-196
6.6.9.5 Inputs/outputs
Commission-
ing
Inputs/outputs
The inputs and outputs can be configured for various functions.
Depending on the hydraulic variant selected, the inputs and outputs are pre-as-
signed, the function can then not be changed [ch. 12.1].
WTC
Parameters
Setting
10.5.1.1
Multifunction sensor
VPT
Deactivate multifunction sensor VPT.
On
(factory setting):
Multifunction sensor VPT activated.
Off
:
Multifunction sensor VPT deactivated.
10.5.1.2
Gas pressure switch
Activate gas pressure switch.
Off
(factory setting):
Gas pressure switch deactivated.
On
:
Gas pressure switch activated.
Only in conjunction with inbuilt gas pressure switch (accessory).
A gas pressure switch is required to ensure the appliance does not go to lockout if
gas pressure fluctuations occur.
10.5.1.3
Output MFA1
Function of output MFA1 [ch. 12.5].
Possible reassignment by commissioning wizard Hydraulic:
Pump HC1
Circulation pump DHW1
10.5.1.4
Input H1
Function of input H1.
10.5.1.5
Input H1 inverted
The function (contact position) of input H1 can be rotated with
inverted
.
normal
inverted
10.5.1.6
Input H2
Function of input H2 [ch. 12.5].
Possible reassignment by commissioning wizard Hydraulic:
DHW 1: circulation/button
10.5.1.7
Input H2 inverted
The function (contact position) of input H2 can be rotated with
inverted
.
normal
inverted
10.5.1.8
Output VA1
Function of output VA1 [ch. 12.5].
10.5.1.9
Output VA2
Function of output VA2 [ch. 12.5].
Possible reassignment by commissioning wizard Hydraulic:
Circulation pump DHW1
10.5.1.10
Input N1
Function of remote control N1 [ch. 12.3].
Off
Load remote control
(function not activated)
Temperature remote control